ABB PowerValue 11 RT

Safeguarding your power supply has never been easier

ABB’s PowerValue 11 RT is simple and cost-effective to install, maintain and expand. For full flexibility it is field configurable in tower format or rack mount. Redundancy or increased system capacity can also be achieved by paralleling the 6 and 10 kVA units. The monitoring solutions give excellent visibility of the system status and enable to remotely supervise the power grid, the battery conditions and the UPS.

Because space in business premises can be at a premium, the PowerValue 11 RT has been designed to be extremely compact. It is also flexible and can be delivered in tower or rack versions to suit your existing infrastructure.

PowerValue has an increased power factor and efficiencies that ensure lower losses. Its advanced technical features also ensures lower battery usage and prolonged lifetime for the UPS batteries meaning that PowerValue 11 is easy on your pocket all round.

PowerValue comes in five different models from 1 to 10 kVA.

The units of the higher-power models (6 and 10 kVA) can be configured in parallel to provide redundancy or to increase the system’s total capacity to 20 kVA. All models can be fitted with up to four matching battery modules to satisfy extended runtime demands. The user-replaceable batteries increase availability and reduce Mean Time to Repair (MTTR).
Order Now!
Standard Features:
  • True online double conversion
  • 0.9 power factor across the entire range
  • Efficiency in online mode up to 93 %
  • Efficiency in eco-mode up to 97 %
  • Configurable in tower format or rack-mount
  • Cold Start available
  • Low installation costs (plug and play)
  • Easy maintenance
  • Frequency converter operation (50 or 60 Hz)
  • Full set of communication interfaces: SNMP, Potential-free contacts, RS-232, USB


General data

System power range

1 kVA – 10 kVA

UPS frame rated power

1 / 2 / 3 / 6 / 10 kVA

UPS output rated PF

0.9

Max. no of parallel frames

Up to 2 units (model dependent)

Wiring

1ph + N + PE

UPS type

Rack or tower convertible

Topology

True online double conversion

Input

Nominal input voltage

208, 220, 230, 240 VAC

Voltage range

110 - 276 VAC (load dependent)

Frequency range

45 - 55 Hz for 50 Hz systems

54 - 66 Hz for 60 Hz systems

Current THD at 100% load

≤5% with linear load

≤7% with nonlinear load

Power Factor at 100% load

≥0.99

Output

Rated output voltage

208, 220, 230, 240 VAC

Voltage THD (with linear load)

≤2% with linear load

≤5% with nonlinear load

Frequency

50 or 60 Hz (selectable)

Efficiency

Online double conversion

Up to 93%

Eco-mode

Up to 97%

Communications

User interface

LCD

Communication ports

USB, RS-232, SNMP slot, potential-free contacts (optional)

Software

Monitoring and shutdown software available as option

Compliancy

Safety

IEC/EN 62040-1

EMC

IEC/EN 62040-2

Performance

IEC/EN 62040-3

Manufacturing

ISO 9001:2008, ISO 14001:2004

 RoHS IEC/EN 50581:2012