ABB Conceptpower DPA 500
Conceived for medium-sized and large data centers, ABB’s Conceptpower DPA 500 modular uninterruptible power supply (UPS) fulfills power requirements from 100 kW to 3 MW and provides maximum availability for those who aim for zero downtime as well as a low cost of ownership.

Total vertical and horizontal scalability The Conceptpower DPA 500 delivers power protection from 100 to 500 kW (one to five modules) in a single cabinet (vertical scalability). Cabinets can operate in a parallel configuration to build a system of up to 3 MW (horizontal scalabiltiy).

True parallel architecture The advanced UPS design of Conceptpower DPA 500 provides the highest degree of protection in critical applications where the load must be fed with quality power. This UPS system utilizes decentralized parallel architecture and ensures the highest level or reliability and availability with true redundancy across the modules.
Order Now!
99.9999% (6 nines) availability
  • Decentralized Parallel Architecture
  • Replace or add modules with no downtime
  • Short mean time to repair
  • No single points of failure

Cost effective "right-sizing"
  • Scalable up to 3 MW
  • Vertical and horizontal scalability

Low total cost of ownership
  • Up to 96% true online efficiency
  • Eco-mode efficiency ≥ 99%
  • Small footprint / high power density
  • Unity power factor (kW = kVA)
  • Low input harmonic distortion (THDi < 3.5%)

Efficient service concept
  • Simple power upgrade
  • Fast maintenance
  • Reduced spare parts needed
  • Full front access

General data 

 400V IEC  480V UL

System power range

100 kW – 3000 kW

UPS module rated power
100 kW

UPS cabinet rated power

500 kW

 300 kW / 500 kW

UPS output rated PF

1.0

Parallel configuration

500 kW Cabinet:
Up to 5 modules
in one cabinet
Up to 6 cabinets
in parallel/3MW






300 kW Cabinet:
Up to 3 modules
in one cabinet
Up to 4 cabinets
in parallel/1.2MW

500 kW Cabinet:
Up to 5 modules
in one cabinet
Up to 6 cabinets
in paralle/3MW

Wiring

3ph + N + PE

3ph + PE

UPS type

Modular, Decentralized Parallel Architecture (DPA)

Topology

Online double conversion

Serviceability Front access only

Input

 400V IEC  480V UL

Nominal input voltage

220/380, 230/400,
240/415 VAC

3 x 480VAC

Voltage range

<  100% (-10%,+15%)
<  80% (-20%,+15%)
<  60% (-30%,+15%)

Frequency range

35-70 Hz 

60 Hz

Current THD at 100% load

< 3.5 %

Power Factor at 100% load

0.99

Output

 400V IEC
 480V UL

Rated output voltage

220/380, 230/400, 240/415 VAC

3 x 480VAC

Voltage THD (with linear load)

< 2 % 

Frequency

50 or 60 Hz (selectable)

 60 Hz

Efficiency

 400V IEC  480V UL

Online double conversion

Up to 96%

>96%

Eco-mode

≥99%

Communications

   

User interface

Graphical touch screen (one per frame as standard) Decentralized LCD + mimic diagram (one per module as standard)

Communication ports (optional)

USB, RS-232, potential-free contacts, SNMP
RS-485, Modbus TCP/IP, SNMP, Bacnet

Customer interface (400 V IEC only)

Remote shutdown, gen-set interface, external bypass contact

Compliancy

 400V IEC  480V UL

Safety

IEC/EN 62040-1

UL 1778 5th edition, CSA C22.2 No. 107.3-14 3rd Ed.

EMC

IEC/EN 62040-2

IEC/EN 62040-2 C3

Performance

IEC/EN 62040-3

IEC/EN 62040-3

Manufacturing

ISO 9001:2008, ISO 14001:2004

ISO 9001:2008